AllMyCalculators

Radiator Size Calculator

Works out the radiator size to specify for a room. Catalogue outputs assume ΔT50; this corrects for the flow temperature you will actually run.

From the heating BTU calculator, or a room-by-room heat loss.

Boiler: 65–75 °C. Heat pump: 35–50 °C, which is why retrofits need bigger radiators.

Radiator to specify, rated at ΔT50
W

Share sends a link that reopens these numbers. Copy details pastes the full breakdown as a list.

The same figure in BTU/h BTU/h
Your actual ΔT K
Output correction factor ×
Reading this

The formula

ΔT = (flow + return) ÷ 2 − room correction = (ΔT ÷ 50)^1.3 rated output = heat required ÷ correction

Radiators are catalogued at ΔT50 — mean water temperature 50 K above the room — so a radiator run cooler than that gives less than its headline figure. The 1.3 exponent is from EN 442 and reflects that a radiator moves heat mostly by convection, which does not scale linearly with temperature difference.

What to watch out for

The correction is the entire point of this page.

  • Catalogue figures are at ΔT50. That means 75 °C flow, 65 °C return, 20 °C room. Almost nobody runs those temperatures any more.
  • Lower flow temperatures need bigger radiators. At ΔT50 a radiator gives 100%. At ΔT30 it gives about 51%, so you need nearly twice the rated output for the same heat.
  • This is why heat pump retrofits change the radiators. A heat pump is efficient because it runs cool, and running cool is exactly what halves a radiator's output. The emitters have to grow to compensate.

Frequently Asked Questions

What size radiator do I need for a room?

Work out the room’s heat loss first, then divide by the correction factor for your flow temperature. A room needing 1,500 W at a ΔT of 40 K needs a radiator rated about 1,960 W at ΔT50.

What is ΔT50 on a radiator?

The standard test condition radiators are rated at: the mean water temperature is 50 K above the room. With a 20 °C room that is 75 °C flow and 65 °C return. Every catalogue output you see assumes it unless stated otherwise.

Do I need bigger radiators for a heat pump?

Usually yes. A heat pump runs at 35–50 °C rather than 70–75 °C, which puts you around ΔT25–ΔT30 instead of ΔT50 — roughly 40–50% of the catalogue output. Radiators typically need to be about twice the size, or replaced with fan-assisted or underfloor emitters.